Measurement of protective earth conductor resistance I=200mA
(protection class I)
Display range
|
Resolution |
Accuracy |
| 0,00...0,99Ω |
0,01Ω |
±(4% m.v. + 2 digits) |
| 1,00...19,99Ω |
±(4% m.v. + 3 digits) |
• test current: ≥200mA for R= 0,2...1,99Ω
• upper limit adjustable in the 10mΩ …1,99Ω range with the 0,01Ω resolution
• measurement time adjustable in 1...60s range, with the 1s resolution
Measurement of protective earth conductor resistance I=10A
(protection class I)
Display range
|
Resolution |
Accuracy |
| 0...999mΩ |
1mΩ |
±(3% m.v. + 4 digits) |
| 1,00...1,99Ω |
0,01Ω |
• technical method
• test current: ≥10A for R≤0,5Ω
• limit adjustable in the 10mΩ …1,99Ω range with the 0,01Ω resolution
• measurement time adjustable in 1...60s range, with the 1s resolution
Measurement of protective earth conductor resistance I=25A
(protection class I)
| Display range |
Resolution |
Accuracy
|
| 0...999mΩ |
1mΩ |
±(3% m.v. + 4 digits) |
| 1,00...1,99Ω |
0,01Ω |
• technical method
• measurement with sinusoidal current of the mains frequency, test current: ≥25A for R≤0,2Ω
• limit adjustable in the 10mΩ …1,99Ω range with the 0,01Ω resolution
• measurement time adjustable in 1...60s range, with the 1s resolution
Measurement of L-N circuit resistance
Display range
|
Resolution |
Accuracy |
| 0...999mΩ |
1mΩ |
±(5% m.v. + 5 digits) |
| 1,00...4,99Ω |
0,01Ω |
• test voltage: 4...8V AC
• short-circuit current: max. 5mA
Measurement of insulation resistance
Measurement range according to IEC 61557-2 for:
UN=100V: 100kΩ...99,9MΩ
UN=250V: 250kΩ...199,9MΩ
UN=500V: 500kΩ...599,9MΩ
| UN |
Display range
|
Resolution |
Accuracy |
| 100V |
0...1999kΩ |
1kΩ |
±(5% m.v. + 8 digits) |
| 2,0...19,99MΩ |
0,01MΩ |
| 20,0...99,9MΩ |
0,1MΩ |
| 250V |
0...1999kΩ |
1kΩ |
| 2,00...19,99MΩ |
0,01MΩ |
| 20,0...199,9MΩ |
0,1MΩ |
| 500V |
0...1999kΩ |
1kΩ |
| 2...19,99MΩ |
0,01MΩ |
| 20,0...599,9MΩ |
0,1MΩ |
• limit adjustable in the: 0.01...9.9mA range with the 0.1MΩ resolution
• adjustable measurement time: continuous measurement (Cont), or from 4s to 3min with 1s resolution
• automatic discharge of the capacity of the tested device after measurement
• protection against measuring live devices
• output current max. 1.4mA
Measurement of PE and residual leakage current:
Display range
|
Resolution |
Accuracy |
| 0,00...3,99mA |
0,01mA |
±(5% m.v. + 2 digits) |
| 4,0...19,9mA |
0,1mA |
• limit adjustable in the 0.01...9.9mA range with the 0.01mA/0.1mA resolution
• adjustable measurement time: continuous measurement (Cont), or 1...60s with 1s resolution
• in the middle of the measurement time, the meter automatically
switches the polarity at the measuring terminal and displays the greater
value
Measurement of equivalent leakage current:
| Display range |
Resolution |
Accuracy |
| 0,00...3,99mA |
0,01mA |
±(5% m.v. + 2 digits) |
| 4,0...19,9mA |
0,1mA |
• limit adjustable in the 0.01...9.9mA range with the 0.01mA/0.1mA resolution
• adjustable measurement time: continuous measurement (Cont), or 1...60s with 1s resolution
• open circuit voltage 25...50V
Measurement of touch leakage current:
| Display range |
Resolution |
Accuracy |
| 0,00...4,999mA |
0,001mA |
±(5% m.v. + 3 digits) |
• limit adjustable in the 0.01...9.9mA range with the 0.01mA/0.1mA resolution
• adjustable measurement time: continuous measurement (Cont), or 1...60s with 1s resolution
• current measurement band 20Hz...100kHz
Measurement of power S:
Display range
|
Resolution |
Accuracy |
| 0...999VA |
1VA |
±(5% m.v. + 3 digits) |
| 1...3,99kVA |
0,01kVA |
• adjustable measurement time: continuous measurement (Cont), or 1...60s with 1s resolution
Measurement of current consumption:
| Display range |
Resolution |
Accuracy |
| 0,00...15,99A |
0,01A |
±(2% m.v. + 3 digits) |
• adjustable measurement time: continuous measurement (Cont), or 1...60s with 1s resolution
Voltage measurement:
| Display range |
Resolution |
Accuracy |
| 187,0…265,0V |
0,01V |
±(2% m.v. + 2 digits) |
„m.v.” measured value
Conforms to the EMC requirements according to EN 61326-1:2006 and EN 61326-2-2:2006.
Electrical safety:
- insulation according to EN 61010-1 and IEC 61557
- measurement category: II 300V acc.to EN 61010-1
- enclosure protection rating acc. to EN 60529: IP40
Other technical specification:
- power supply: 187...265V, 50Hz
- load current: max. 16A (230V)
- measurement results memory: 990 cells
- data transmission to PC: USB
- dimensions: 330 x 235 x 120mm
- weight: about 4,75kg
- operating temperature: 0...+40°C
- storage temperature: -20...+70°C
- humidity: 20...80%